Compact microprocessor controlled fire control panel for the use with the CT 3000 fire detection system components. Approved according to EN 54-2: 1997/A1: 2006 and EN 54-4: 1997/A2: 2006
Clear display and easy operation with LED displays and operation keys
Connection possibility for 8 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone
Extension option via 4 zone modules for up to 16 conventional zones for CT 3000 fire detection components
Integrated power supply according to EN 54-4:A2 2006
Independent connection of detector and signalling device zones
Integrated "one-man-revision mode"
Manual control of signalling devices via seperate input
Programming options such as alarm delay
Panel network of max. two fire control panels
Supply Voltage: 230 V AC ( ±10 %)
Emergency Supply: 1 x 12 V / 18 Ah
Quiescent Current: 2 to 10 mA
Alarm Current: 10 mA to 110 mA
Output: 4 x 24 V/300 mA monitored for siglanling devices; 2 relay outputs 60 V DC/120 V AC/3A for alarm and fault
Ambient Temperature: -5°C to +40°C
Humidity: max. 95%
Protection class: IP 30
Dimensions (H x W x D): 345 mm x 455 mm x 128 mm
Weight: 4,26 kg (w/o battery)
Material: ABS, Glass
Standards: EN 54-2: 1997/A1: 2006; EN 54-4: 1997/A2: 2006
CE-CPD-Number: 1293-CPD-0175
Further Approvals: EVPU 1293-CPD-0175
Remarks = Accessories: part-no. 32653, Type GE 4: 4 zone extension, part-no. 32654, Type SE 4: 4 signaling device lines extension, part-no. 32655, Type RM8: relay-module, 8 relay 1 A/12 V
Display: 16 LEDs for status indication - (additionally 8 LEDs with etension); 6 keys for operation and programming
Power Supply: 24 V DC/1 A